Fire Science Popularization | Detailed Explanation of Code for Acceptance and Inspection of Fire Extinguisher Configuration in Buildings


Acceptance method: visual inspection on site, checking the relevant quality certificates of the product.

Inspection quantity: 20% randomly selected, but not less than 3; Less than 3 full inspections.

Inspection and Maintenance 5.1 General Provisions 5.1.1 The inspection and maintenance of fire extinguishers shall be undertaken by relevant technical personnel.

The as-built drawing of the building fire extinguisher configuration project, and the location code table of the building fire extinguisher configuration; 2.

Inspection quantity: random sampling 20%.

4.2 Configuration acceptance 4.2.1 The type, specification, fire extinguishing level, and configuration quantity of fire extinguishers should meet the design requirements for building fire extinguisher configuration.

Acceptance method: observation, inspection and actual measurement.

Inspection quantity: all inspections.

Acceptance method: Compare with the design drawing of fire extinguisher configuration in the building.

Inspection quantity: 20% randomly selected, but not less than 3; Less than 3 full inspections.

4.2.7 The hooks and brackets of fire extinguishers shall comply with the provisions of Clauses 3.2.4 to 3.2.6 of this specification.

Song, dance, entertainment, screening, entertainment venues, Class A and Class B fire hazard sites, cultural relics protection units, all inspected.

Acceptance method: observation and inspection.

Scaffolding Adjustable Base Jack

Relevant quality certificates, factory certificates, operation and maintenance instructions, etc.

Inspection quantity: random sampling inspection of 5%, but not less than 3; Less than 3 full inspections.

4.2.3 When different types of fire extinguishers are used within the same fire extinguisher configuration unit, their extinguishing agents should be compatible.

Corresponding protective measures shall be taken for fire extinguishers installed outdoors and in special places.

4.2.9 The setting of wheeled fire extinguishers shall comply with the provisions of 3.3.1 and 3.3.2 of this specification.

Acceptance method: observation and inspection.

Inspection quantity: all inspections.

4.2.4 The protection distance of fire extinguishers should comply with the relevant provisions of the current national standard “Code for Design of Extinguisher Distribution in Buildings” GB50140.

Acceptance method: observation, inspection and actual measurement.

When exceeding the limit, a fire extinguisher of the same type and operation method should be selected for replacement.

Inspection quantity: all inspections.

4.2.2 The product quality of fire extinguishers must meet the requirements of relevant national product standards.

of fire extinguishers.

Code for Acceptance and Inspection of Fire Extinguisher Configuration in Buildings 4.1 General Provisions 4.1.1 After installation and installation of fire extinguishers, configuration acceptance must be conducted, and unqualified fire extinguishers cannot be put into use.

The fire extinguishing level of the replacement fire extinguisher should not be lower than that of the original configured fire extinguisher.
.

4.2.8 When the fire extinguisher is installed using hooks, brackets, or wall mounted fire extinguisher boxes, the height of the fire extinguisher should comply with the requirements of the current national standard “Code for Design of Extinguisher Distribution in Buildings” GB50140, and the vertical deviation between the setting point and the design point should not be greater than 0.01 m.

Is the fire extinguisher inspected once a month? Or once a month? Based on what? Fire extinguishers are the most common fire-fighting facilities, and they are also the most effective facilities for extinguishing fires and controlling their spread during the early stages of a fire.

The qualification criteria should be: A=0, B ≤ 1, and B+C ≤ 4, otherwise it is considered as unqualified.

The setting of fire extinguishers should ensure that any point in the configuration site is within the protection range of the fire extinguisher setting point.

4.1.4 The acceptance report of fire extinguisher configuration in buildings shall be filled out according to the requirements of Appendix B of this specification.

5.1.2 The number of fire extinguishers sent for repair each time shall not exceed 1/4 of the total number of fire extinguishers configured in the calculation unit.

4.2.11 The placement of fire extinguishers should be stable.

Inspection quantity: randomly inspect 20% of the total number of fire extinguisher configuration units; If there are less than 3 configuration units, check them all.

Inspection quantity: all inspections.

Inspection quantity: randomly inspect 20% to check the appearance quality of the fire extinguisher.

4.2.5 There should be no obstacles near the fire extinguisher setting point, and the access to the fire extinguisher should be convenient, and it should not affect the safe evacuation of personnel.

Acceptance method: observation and inspection.

4.1.2 The acceptance of fire extinguisher configuration shall be conducted by the design, installation, supervision, and other units organized by the construction unit in accordance with the building fire extinguisher configuration design documents.

4.1.3 During the acceptance of fire extinguisher configuration, the installation unit shall submit the following technical data: 1.

Through various promotions, studies, and inspections, it is now known that fire extinguishers should be inspected once a month, and some key locations require inspection every half month.

4.3 Configuration acceptance judgment rules 4.3.1 Fire extinguisher configuration acceptance shall be conducted according to independent buildings, and partial acceptance can be conducted according to the scope of application.

Defect items shall be divided into serious defect items (A), serious defect items (B), and minor defect items (C) according to Appendix B of this specification.

Acceptance method: observation and inspection.

Inspection quantity: randomly inspect 20% of the total number of fire extinguisher configuration units, and no less than 3; If there are less than 3 configuration units, check them all.

4.3.2 The determination rules for fire extinguisher configuration acceptance shall meet the following requirements: 1.

Acceptance method: Measure with a ruler.

Is the management of fire extinguishers just checked once a month? Today, we will sort out some regulatory requirements from the aspects of configuration acceptance, inspection, and maintenance of building fire extinguishers.

Acceptance method: Compare the fire extinguisher configuration design documents and fire extinguisher nameplates in the building and verify them on site.

4.2.6 The fire extinguisher box shall comply with the provisions of Clauses 3.2.2 and 3.2.3 of this specification.

Acceptance method: observation, inspection and actual measurement.

4.2.10 The location identification of fire extinguishers shall comply with the provisions of 3.4.1 and 3.4.2 of this specification.

Description of fire extinguisher configuration design, and review opinions on building design fire prevention; 3.

The setting point of the fire extinguisher should be ventilated, dry, and clean, and its ambient temperature should not exceed the operating temperature range of the fire extinguisher.

Check the qualification procedures of all fire extinguishers.